undefined
undefined
+
  • undefined
  • undefined

Micro Power 3000W MPUK-4860


  • 产品描述
    • Commodity name: Micro Power 3000W MPUK-4860

    Introduction

    • The Micro Power series DC power supplies are specially designed for telecom industry serving as power and backup system with safety features and protection functions such as battery over/under voltage, over current, short-circuit, and over/under temperature, and surge protection. They offer complete maintenance-free and extensive monitoring and controlling capabilities.
    • MPUK-4860 is a 3kW power supply unit integrated with 50Ah lithium battery backup. The system is featured with die-cast aluminum enclosure, embedded BMS, easy for installation and maintenance, supporting pole/wall-mounting. It is mostly suitable as power and backup solutions for pole/wall mounted telecom applications.

     

    Features

    • Including all the features of switching mode power supply;
    • Integrated molding with die-cast aluminum to provide good protection;
    • Flexible and convenient installation, supporting pole/wall mounting;
    • 50Ah Li-ion battery backup, support battery expansion;
    • Remote monitoring through RS485

     

    Technical Specifications

    Technical Specifications
    Basic Parameters Dimensions 420 x 320 x 90 mm (H x W x D)
    Protection Level IP65
    Weight Power: ≤ 15 KG
    Basic Parameters 
    (cont.)
    Material  Die-cast Aluminum for enclosure body 
    Working Temperature  -40  – +55  
    Storage Temperature  -40  – +60  
    Relative Humidity  10 – 95% 
    Cooling Method  Natural Cooling 
    Atmospheric Pressure  70-106 kPa 
    Input Input Voltage Range  90 – 280 VAC 
    Input Frequency Range  45 – 65 HZ 
    SPD (Input Side)  In = 20 kA8/20 μs 
    Input Current  Max.13 A 
    Output Normal Output Voltage  56.4 VDC 
    Output Voltage Range  43 – 58 VDC (adjustable) 
    Output Power  3000 W 
    Output Current  35.4 A 
    Number of Current Outputs  3*60 A 
    Efficiency  ≥ 95%(Rated 220 input, load rate 50-100%) 
    Load Regulation  ≤ ±0.5% 
    Cross Regulation  ≤ ±0.6% 
    Standards CB  IEC/EN 62368-1 
    EMC  ETSI EN 300 386 
    CE  LVD Directive 2014/35/EU 
    EMC Directive 2014/30/EU 
    RoHS Directive 2011/65/EU 


     

     

Online consultation