- 产品描述
-
- Commodity name: Kexin Indoor 5G CRAN Intelligent Module Solution
Kexin Indoor 5G CRAN intelligent module solution adopt modular design, integrating cabinets、energy and environmental monitoring system, power supply system, battery system, fire fighting system, refrigeration system, and a system for isolating hot and cold areas, Effectively solve problems such as long construction cycles, hot zones, high PUE values, and difficulties in operation and maintenance.
✅ Rapid station building, one-stop integrated and standardized design, modular replication, to meet the requirements of rapid station building;
✅ Increase the volume ratio of the machine room, and put the supporting equipment into the cabinet, with a small floor area, so as to improve the utilization ratio of 4 / 5G co built machine room;
✅ Safety and stability, pre installation and commissioning of the whole plant, intelligent operation and maintenance monitoring;
✅ The construction is simple, the site only needs to be simple and parallel, the construction is completed in 4 hours, the business is online in 2 days, the construction cost is reduced, and the construction cost is saved;
✅ Cabinet level refrigeration, energy-saving and high efficiency, pue value as low as 1.35, reduce operation cost.
The 5G C-RAN intelligent module series products can be flexibly deployed in single or multiple cabinets,according to the area of the computer room、the quantity of equipment and the situation of power supply.Suitable for various Base station rooms and expansion, access area rooms, aggregation rooms, etc.
Model Single-cabinet Double-cabinets Multiple-caninets Specifications W*D*H=800*600*2200mm W*D*H=(800*2)*600*2200mm W*D*H=(800*N)*600*2200mm Equipment capacity Available space, 19 "47U Available space, 19 "2*47U Available space, 19 "N*47U BBU Total installation space of 12U
BBU equipment
Up to 4 BBU can be configured
(2U each + 1U air duct)
Total installation space of 24U
BBU equipment
Up to 8 BBU can be configured
(2U each + 1U air duct)
Total installation space of 12N U
BBU equipment
4N BBU can be configured
(2U each + 1U air duct)
Reserved space Reserve 5U transmission
equipment installation space
Can install ipran device, OLT
device, dynamic capacity
expansion
Reserve 12U transmission
equipment installation space
Can install ipran device, OLT
device, dynamic capacity
expansion
Reserve 20U transmission
equipment installation space
Can install ipran device, OLT
device, dynamic capacity
expansion
Switch Power Supply 48V200A,efficiency 96% 48V400A,efficiency 96% 48V600A,efficiency 96% lithium iron
phosphate battery
48V100Ah*2 48V100Ah*4 48V100Ah*2N DCDU 48V/160A*1 48V/160A*3 48V/160A*N Monitoring 1U monitoring (door magnet,
temperature and humidity,
smoke sense, water immersion
, etc.)
Door magnetism, temperature
and humidity, smoke sensing,
water immersion, remote
signaling and telemetry
Door magnetism, temperature
and humidity, smoke sensing,
water immersion, remote
signaling and telemetry
Air-con refrigeration Frame air conditioner, cooling
capacity 4kw, power consump
tion 1.3kw
Frame air conditioner,
cooling capacity 8kw,
power consumption 2.6kw
Frame type air conditioner,
cooling capacity 8kw/(N/2-1)
sets, power consumption 2.6Nkw
Emergency ventilation DC fan is set inside the top
cover
DC fan is set inside the top
cover
DC fan is set inside the top
cover
Air distribution The cold and hot channels are
completely isolated;
4 sets Compatible wind guide
design (invention patent)
The cold and hot channels
are completely isolated;
8 sets Compatible wind guide
design (invention patent)
The cold and hot channels
are completely isolated;
4N sets Compatible wind guide
design (invention patent)
Follow us
Stock Code:300565